FWD-2000-T3-230

These finned tubular heaters are designed for use in small work or storage areas which are located in zone 1 and 2 or zone 21 and 22 hazardous areas where the flammable atmosphere is a IIA, IIB or IIC gas group. The FWDT range comes with an easy to adjust external thermostat 0-40°C.

FWD-2000-T3-230
Show photo

Product specifications

Order refer. FWD-2000-T3-230
Housing lightweight coated mild steel
Power 2000W
Temperature class T3
Max. surface temp. 200°C
Thermostat 0
Cable entry 2 x M20
Weight 20 kg
Ex Certificate LCIE04ATEX6016X

Classification

  • II 2 G Ex d IIC T2-T4 Gb
  • II 2 D Ex t IIIC IP66 T300°C-T135°C Db

Zone

0 1 2
20 21 22

General technical specifications

Protection IP66
Elements individually replaceable
Voltage 230-254V
Mounting floor or wall mounting by means of supplied mounting feet
Ambiant temperature -60°C - +40°C
Guideline ATEX
Manufacturer ExHeat
Suited for
Zone 1 Zone 2
Zone 21 Zone 22

Dimensional sketches

Product code Dimensions
A B
FWD-2000-T3-230 2450 2320